In a sandwich panel building, the middle of the panel is usually the strongest part of the envelope. The weak points are panel joints, roof-wall junctions, openings, and places where metal crosses the insulation layer. Air leakage and thermal bridges should be measured before panels are replaced. The sound order: measure in cold weather, seal on the warm side, correct details, and only then decide on replacement.
Problem
The heating runs, yet the hall does not stay warm
As temperatures fell in late October, the head of the National Iranian Gas Company reported a sharp jump in gas use within days and said some industrial units may need alternative fuels on peak-demand days. For the owner of a heated factory, warehouse, or hall, that news raises a practical question: how much of the heat being produced does the building envelope actually keep? The symptoms are familiar. The top of the hall is warm while the floor is cold, draughts are felt near loading doors, heaters run longer than expected, and staff complain about cold along the walls. The usual reaction is to blame thin panels and propose replacement or extra insulation. But a panel with good thermal resistance on paper is only one component of the real envelope. If warm air leaves through joints and cold air enters under doors, even a good number on the data sheet does not describe how the building behaves.
- A noticeable temperature difference between the roof zone and the working level indicates stratified warm air, and any leakage high in the hall makes that loss worse.
- Cold draughts at low level, even with doors shut, usually point to air leakage at the wall base, around doors, or along panel joints.
- Dark lines or staining along joints and junctions can indicate continuous airflow depositing dust and should be investigated.
- Frost or snow melting early in regular lines on the roof may reveal where heat is escaping beneath the covering.
- Local drips or dampness under joints in cold weather may come from humid air leaving through the joint rather than from rain getting in.
Engineering cause
A panel is not a continuous layer: joints and junctions decide how the envelope behaves
The steel faces of a sandwich panel are effectively airtight, so the real question lies at the joints between panels and at their connections to other components. European research on steel sandwich panels has shown that joints and openings can downgrade the thermal performance of the envelope, and found that air permeability depends on three factors: joint geometry, the right sealing tape, and fabrication and mounting tolerances. The same work stresses that exact mounting of the tape is decisive, and that excellent airtightness is achievable with correct detailing. In calculations the two effects are not separate either: researchers combine transmission through the panel with losses from air movement in a single effective heat transfer coefficient for approximate energy calculations. While the hall is heated, that airflow always has a driving force. In a high, warm volume, warm air rises and pushes outward at the upper level, while cold air replaces it from below. Wind adds its own pressure on top, and on windy days its effect is sometimes the larger one. The more gaps remain open at top and bottom, the greater the airflow. The second factor is thermal bridging, where metal or another conductive part carries heat past the insulation.
- A longitudinal joint with incorrect spacing, twisted sheet, or missing or displaced tape creates a continuous path for air.
- Roof-wall junctions, ridges, and wall bases usually rely on flashings, and if the space behind the flashing is not filled and air-sealed, it protects only against rain, not air.
- Panel cut-outs for ducts, pipes, vents, or rooflights that are closed without sealing and insulation details leak air and also break insulation continuity.
- Penetrating metal parts such as canopy brackets, service supports, and long fasteners create point or linear thermal bridges.
- Loading and industrial doors left open too long or fitted with worn seals can sometimes move more air than all the envelope joints together.
- Rushed installation and structural settlement over time can open a joint that was closed on handover day, so periodic inspection is needed.
Technical proof or diagram
Technical proof state
No metric, project result, or proof image is shown until a verified asset is attached.
The verified diagram should show a building section: warm air rising and leaving at the ridge and junctions, cold air entering at the wall base and doors, and thermal bridges at penetrating parts. This technical asset is still pending verification.
- Longitudinal joint and sealing tape
- Ridge and roof-wall junction
- Wall base and door perimeter
- Penetrating metal parts and thermal bridges
SIPANEL solution logic
SIPANEL logic for reducing heat loss before replacing panels
Gather documents and symptoms
As-built drawings, panel and core specifications, junction details, heating type, and door-use patterns are reviewed. Operator reports of cold spots, draughts, and drips are recorded on the plan so the survey does not begin with guesswork.
Survey in suitable measurement conditions
Thermography is carried out in cold weather with the heating on, so that the temperature difference is sufficient. Suspect points are confirmed with smoke testing or, where feasible, a fan pressure test. Each point is logged with a photo and plan location, because a thermal image without interpretation can mislead.
Separate air leakage from thermal bridges and weak insulation
Each finding is traced to its root: airflow, a conductive part, a damaged core, or missing insulation behind a flashing. This distinction decides whether the answer is air sealing, detail correction, or local panel replacement.
Correct in order of effect and risk
Unless the measurements show otherwise, doors and large openings usually come first, then ridges and wall bases, then joints and penetrations. The governing principle is to air-seal on the warm side and keep the drainage path open on the cold side. Any new material must be compatible with the core type, the facings, and the project's fire requirements.
Coordinate with building services
Heater positions, destratification, air curtains, and door operation are decided with the mechanical designer. Tightening the envelope can change ventilation needs and indoor humidity, and where gas heaters draw combustion air from the hall, that supply must also be checked, so these are reviewed at the same time.
Verify after correction and plan inspections
The same points are checked again after correction under similar conditions, and the result is recorded. A periodic inspection plan is defined for joints, junctions, and busy doors so that wear and settlement are caught in time.
Technical FAQ
View complete FAQDoes a thicker panel solve heat loss?
Not necessarily. Greater thickness reduces loss through the middle of the panel but does nothing for air leakage at joints and junctions. If details are the main escape route, replacing panels adds cost and may repeat the problem in the new details. Measurement should first show which route matters most.
How do we find air leaks in an industrial building?
Combining cold-weather thermography, visual inspection of joints and flashings, and smoke testing gives the most practical information. Where possible, a fan pressure test shows overall airtightness. A thermal image alone is not enough, because shiny surfaces reflect and a cold spot may be a thermal bridge rather than a leak.
When should a thermal survey be done?
When the heating has been on for some time and the indoor-outdoor temperature difference is significant, usually before sunrise or after sunset, when the sun has not been warming the surface and the wind is light. That is why the cold months are the right time to collect data.
Can joints be filled with spray foam?
It is not recommended as a general fix. Foam may block drainage paths, fail to bond durably to the facing or coating, crack with thermal movement, and create problems with fire requirements. The choice of tape, mastic, or insulation should follow the connection detail, the core type, and the project's fire requirements.
What does heat loss have to do with condensation and drips?
Warm, humid air leaving through a joint meets a cold surface on its way out, and if that surface is below the air's dew point, its moisture condenses. That water may appear as drips or stay around the joint and be mistaken for a rain leak. So air-sealing on the warm side both saves energy and reduces moisture risk.
Can the energy saving be predicted in advance?
There is no reliable general figure, because the result depends on climate, hall height, operating pattern, heating type, and the current state of the joints. A credible estimate comes from measuring the existing condition and comparing consumption before and after correction under similar conditions.
Related Engineering Resources
Open resource hubA decision guide for choosing panel type, core material, thickness, joint logic, insulation level, and procurement inputs before ordering.
Shop Drawing Review Guide for Panel ProjectsA structured guide for checking panel layout, accessories, flashing logic, quantities, and execution coordination.
Mehrabad Aircraft HangarAircraft Hangar
32-Bed Military HospitalEmergency hospital — Full EPC delivery
Kermanshah Industrial University Petroleum FacultyStructural Glass Facade
Related Services and Insights
Panel selection, procurement coordination, and installation control.
Why Sandwich Panel Joint Logic Controls Leakage RiskRooflight Dripping in Autumn: Leak or Condensation?Falls through rooflights on industrial roofs in winter workInsights IndexReturn to all engineering insights.
CTA
Before replacing panels, identify where the heat is going
Send your drawings, panel specifications, photos of joints and junctions, and any reports of cold spots, draughts, or drips, so the SIPANEL technical team can review the envelope and propose the order of detail corrections.